Accepted originator categories for PSTO
If the requested command is accepted by the authority control, the value will
change. Otherwise the attribute
blocked-by-switching-hierarchy
is set in the
cause
signal. If the PSTO value is changed during a command, then the command is
aborted.
The accepted originator categories for each PSTO value are shown in
.
Table 48:
Accepted originator categories for each PSTO
Permitted Source To Operate
Originator (orCat)
0 = Off
4,5,6
1 = Local
1,4,5,6
2 = Remote
2,3,4,5,6
3 = Faulty
4,5,6
4 = Not in use
4,5,6
5 = All
1,2,3,4,5,6
6 = Station
2,4,5,6
7 = Remote
3,4,5,6
PSTO = All, then it is no priority between operator places. All operator places are
allowed to operate.
According to IEC 61850 standard the
orCat
attribute in originator category are
defined in
Table 49:
orCat attribute according to IE C61850
Value
Description
0
not-supported
1
bay-control
2
station-control
3
remote-control
4
automatic-bay
5
automatic-station
6
automatic-remote
7
maintenance
8
process
15.3.2
Bay control QCBAY
M16595-3 v10
The Bay control (QCBAY) is used to handle the selection of the operator place per
bay. The function gives permission to operate from two main types of locations
either from Remote (for example, control centre or station HMI) or from Local
1MRK 506 369-UEN B
Section 15
Control
Line distance protection REL670 2.2 IEC
643
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...