and the set definite time delay. Thus, if only the inverse time delay
is required, it is important to set the definite time delay for that
stage to zero.
9.5.3.1
Settings for each step
GUID-CFB327EF-C5C4-44B5-AB4B-9C2916355FC5 v5
x means step 1, 2, 3 and 4.
DirModeSelx
: The directional mode of step x. Possible settings are off/
nondirectional/forward/reverse.
Characteristx
: Selection of time characteristic for step
x
. Definite time delay and
different types of inverse time characteristics are available.
Table 37:
Inverse time characteristics
Curve name
ANSI Extremely Inverse
ANSI Very Inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI/IEEE Definite time
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG (logarithmic)
The different characteristics are described in the Technical Reference Manual
(TRM).
Ix>
: Operation negative sequence current level for step x given in % of
IBase
.
1MRK 506 369-UEN B
Section 9
Current protection
Line distance protection REL670 2.2 IEC
491
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...