needs to be connected only if the trip function block has been selected to give
1ph/2ph/3ph trip and an auto reclosing cycle with two phase reclosing is foreseen.
TRSOTF
This is the signal “Trip by Switch Onto Fault”. It is usually connected to the
“switch onto fault” output of line protection if multi-shot auto reclosing attempts
are used. The input will start the shots two to five.
WAIT
Used to hold back reclosing of the “low priority unit” during sequential auto
reclosing. See “Recommendation for multi-breaker arrangement” below. The signal
is activated from output
WFMASTER
on the second breaker auto recloser in multi-
breaker arrangements.
ZONESTEP
The
ZONESTEP
input is used when coordination between local auto reclosers and
down stream auto reclosers is needed. When this input is activated the auto recloser
increases its actual shot number by one and enters “reclaim time” status. If a start is
received during this reclaim time the auto recloser is proceeding as usual but with
the dead time for the increased shot number. Every new increase of the shot
number needs a new activation of the
ZONESTEP
input. This functionality is
controlled by the setting
ZoneSeqCoord
.
Recommendations for output signals
M12399-46 v9
Please see Figure
and default factory configuration
for examples.
1PT1 and 2PT1
Indicates that single-phase or two-phase auto reclosing is in progress. It is used to
temporarily block an earth-fault and/or pole disagreement function during the
single-phase or two-phase open interval.
3PT1, 3PT2, 3PT3, 3PT4 and 3PT5
Indicates that three-phase auto reclosing shots one to five are in progress. The
signals can be used as an indication of progress or for own logic.
ABORTED
The
ABORTED
output indicates that the auto recloser is inhibited while it is in one
of the following internal states:
•
inProgress: auto recloser is started and dead time is in progress
•
reclaimTimeStarted: the circuit breaker closing command has started the
reclaim timer
•
wait: an auto recloser, acting as slave, is waiting for a release from the master
to proceed with its own reclosing sequence
Section 15
1MRK 506 369-UEN B
Control
628
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...