RFFwPP
Z
R
X
load
≤
⋅
⋅
∂ −
⋅
∂
1 6
1
1
.
cos
sin
min
IEC13000276 V1 EN-US
(Equation 145)
Set the fault resistance coverage RFRwPP and RFRwPE to the same value as in
forward direction, if that suits the application. All this is applicable for all
measuring zones when no Power swing detection function ZMRPSB is activated in
the IED. Use an additional safety margin of approximately 20% in cases when a
ZMRPSB function is activated in the IED, refer to the description of Power swing
detection function ZMRPSB.
8.3.3.8
Load impedance limitation, with Phase selection with load
encroachment, quadrilateral characteristic function activated
SEMOD55087-138 v5
The parameters for shaping of the load encroachment characteristic are found in the
description of Phase selection with load encroachment, quadrilateral characteristic
function (FDPSPDIS).
8.3.3.9
Setting of minimum operating currents
SEMOD55087-141 v5
The operation of Distance protection zone, quadrilateral characteristic (ZMQPDIS)
can be blocked if the magnitude of the currents is below the set value of the
parameter
IMinOpPP
and
IMinOpPE
.
The default setting of
IMinOpPP
and
IMinOpPE
is 20% of
IBase
where
IBase
is
the chosen current for the analogue input channels. The value has been proven in
practice to be suitable in most of the applications. However, there might be
applications where it is necessary to increase the sensitivity by reducing the
minimum operating current down to 10% of
IBase
. This happens especially in
cases, when the IED serves as a remote back-up protection on series of very long
transmission lines.
Setting
IMinOpIN
blocks the phase-to-earth loop if 3I
0
<
IMinOpIN
. The default
setting of
IMinOpIN
is 5% of
IBase
.
The minimum operating fault current is automatically reduced to 75% of its set
value, if the distance protection zone has been set for the operation in reverse
direction.
8.3.3.10
Directional impedance element for quadrilateral characteristics
M16923-139 v6
The evaluation of the directionality takes place in Directional impedance
quadrilateral function ZDRDIR. Equation
that the fault is in forward direction for phase-to-earth fault and phase-to-phase
fault.
Section 8
1MRK 506 369-UEN B
Impedance protection
232
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...