Figure 269:
Step 2, selectivity calculation
A second criterion for step 2 is according to equation
1
1
0
step2
step1
0
3I
I
.2
I
3I
³
×
×
EQUATION1203 V4 EN-US
(Equation 465)
where:
I
step1
is the current setting for step 1 on the faulted line.
Step 3
M15282-164 v6
This step has directional function and a time delay slightly larger than step 2, often
0.8 s. Step 3 shall enable selective trip of earth faults having higher fault resistance
to earth, compared to step 2. The requirement on step 3 is selectivity to other earth-
fault protections in the network. One criterion for setting is shown in Figure
.
IEC05000156-3-en.vsd
IN
>
One phase-to-
earth fault
3I
0
IN
>
3I
02
IEC05000156 V3 EN-US
Figure 270:
Step 3, Selectivity calculation
1
0
step3
step2
02
3I
I
.2
I
3I
³
×
×
EQUATION1204 V4 EN-US
(Equation 466)
where:
I
step2
is the chosen current setting for step 2 on the faulted line.
1MRK 506 369-UEN B
Section 9
Current protection
Line distance protection REL670 2.2 IEC
487
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...