IEC07000198 V3 EN-US
Figure 427:
Configuration for using an instance in task time group 1 as DFT
reference
Assume instance SMAI7:7 in task time group 1 has been selected in the
configuration to control the frequency tracking . Observe that the selected reference
instance (i.e. frequency tracking master) must be a voltage type. Observe that
positive sequence voltage is used for the frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
numbering):
SMAI1:1:
DFTRefExtOut
=
DFTRefGrp7
to route SMAI7:7 reference to the
SPFCOUT output,
DFTReference
=
DFTRefGrp7
for SMAI1:1 to use SMAI7:7 as
) SMAI2:2 – SMAI12:12:
DFTReference
=
DFTRefGrp7
for SMAI2:2 – SMAI12:12 to use SMAI7:7 as reference.
For task time group 2 this gives the following settings:
SMAI1:13 – SMAI12:24:
DFTReference
=
ExternalDFTRef
to use DFTSPFC
input of SMAI1:13 as reference (SMAI7:7)
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
DFTReference
=
ExternalDFTRef
to use DFTSPFC
input as reference (SMAI7:7)
Example 2
Section 24
1MRK 506 369-UEN B
Basic IED functions
866
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...