8.12.3.8
Zone reach setting higher than minimum load impedance
GUID-78D0227F-2568-4C9A-8921-45812B4ABAF2 v5
The impedance zones are enabled as soon as the (symmetrical) load impedance
crosses the vertical boundaries defined by
RLdFw
and
RLdRv
[4]
or the lines
defined by
ArgLd
. So, it is necessary to consider some margin. It is recommended
to set
RLdFw
and
RLdRv
to 90% of the per-phase resistance that corresponds to
maximum load.
min
0.9
load
RLdFw
R
<
×
IECEQUATION2419 V2 EN-US
(Equation 331)
min
0.9
load
RLdRv
R
<
×
IECEQUATION2420 V2 EN-US
(Equation 332)
The absolute value of the margin to the closest
ArgLd
line should be of the same
order, that is, at least 0.1 • Z
load min
.
The load encroachment settings are related to a per-phase load impedance in a
symmetrical star-coupled representation. For symmetrical load or three-phase and
phase-to-phase faults, this corresponds to the per-phase, or positive-sequence,
impedance. For a phase-to-earth fault, it corresponds to the per-loop impedance,
including the earth return impedance.
R
X
RLdFw
RLdRv
ArgLd
90%
10%
10%
ARGLd
Possible
load
ARGLd
ARGLd
R
X
RLdFw
RLdRv
X
L
d
X
L
d
ARGLd
ARGLd
ARGLd
ARGLd
IEC12000176-2-en.vsd
IEC12000176 V2 EN-US
Figure 181:
Load impedance limitation with load encroachment
During the initial current change for phase-to-phase and for phase-to-earth faults,
operation may be allowed also when the apparent impedance of the load
encroachment element is located in the load area. This improves the dependability
for fault at the remote end of the line during high load. Although it is not associated
to any standard event, there is one potentially hazardous situation that should be
considered. Should one phase of a parallel circuit open a single pole, even though
there is no fault, and the load current of that phase increase, there is actually no
way of distinguish this from a real fault with similar characteristics. Should this
[4] RLdRv=RLdRvFactor*RLdFw
Section 8
1MRK 506 369-UEN B
Impedance protection
354
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...