accidental event be given precaution, the phase-to-earth reach (RFPEZx) of all
instantaneous zones has to be set below the emergency load for the pole-open
situation. Again, this is only for the application where there is a risk that one
breaker pole would open without a preceding fault. If this never happens, for
example when there is no parallel circuit, there is no need to change any phase-to-
earth reach according to the pole-open scenario.
8.12.3.9
Other settings
GUID-9D65B411-6FE2-433B-AE6C-C6DD716D1181 v7
IMinOpPEZx
and
IMinOpPPZx
The ability for a specific loop and zone to issue a start or a trip is inhibited if the
magnitude of the input current for this loop falls below the threshold value defined
by these settings. The output of a phase-to-earth loop Ln is blocked if ILn <
IminOpPE
(Zx). In is the RMS value of the fundamental current in phase n.
The output of a phase-to-phase loop LmLn is blocked if ILmLn <
IMinOpPP
(Zx).
ILmLn is the RMS value of the vector difference between phase currents Lm and
Ln.
Both current limits
IMinOpPEZx
and
IMinOpPPZx
are automatically reduced to
75% of regular set values if the zone is set to operate in reverse direction, that is,
OperationDir
is set to
Reverse
.
OpModePPZx
and
OpModePEZx
These settings, two per zone (x=1,2..5&RV), with options {Off, Quadrilateral,
Mho, Offset}, are used to set the operation and characteristic for phase-to-earth and
phase-to-phase faults, respectively.
For example, in one zone it is possible to choose Mho characteristic for the three
Ph-Ph measuring loops and Quadrilateral characteristic for the three Ph-E
measuring loops.
DirModeZx
This setting defines the operating direction for zones Z3, Z4 and Z5 (the
directionality of zones Z1, Z2 and ZRV is fixed). The options are
Non-directional
,
Forward
or
Reverse
. The result from respective set value is illustrated in figure
,
where the positive impedance corresponds to the direction out on the protected
line.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
355
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...