For this example with a fault between T and B, the measured impedance from the T
point to the fault will be increased by a factor defined as the sum of the currents
from T point to the fault divided by the IED current. For the IED at C, the
impedance on the high voltage side U1 has to be transferred to the measuring
voltage level by the transformer ratio.
Another complication that might occur depending on the topology is that the
current from one end can have a reverse direction for fault on the protected line.
For example, for faults at T the current from B might go in reverse direction from
B to C depending on the system parameters (see the dotted line in figure
given that the distance protection in B to T will measure wrong direction.
In three-end application, depending on the source impedance behind the IEDs, the
impedances of the protected object and the fault location, it might be necessary to
accept zone 2 trip in one end or sequential trip in one end.
Generally for this type of application it is difficult to select settings of zone 1 that
both gives overlapping of the zones with enough sensitivity without interference
with other zone 1 settings, that is, without selectivity conflicts. Careful fault
calculations are necessary to determine suitable settings and selection of proper
scheme communication.
Fault resistance
M17048-597 v8
The performance of distance protection for single phase-to-earth faults is very
important, because normally more than 70% of the faults on transmission lines are
single phase-to-earth faults. At these faults, the fault resistance is composed of
three parts: arc resistance, resistance of a tower construction, and tower-footing
resistance. The arc resistance can be calculated according to Warrington's formula:
1.4
28707 L
Rarc
I
×
=
EQUATION1456 V1 EN-US
(Equation 126)
where:
L
represents the length of the arc (in meters). This equation applies for the distance protection
zone 1. Consider approximately three times arc foot spacing for the zone 2 and to give extra
margin to the influence of wind speed and temperature.
I
is the actual fault current in A.
In practice, the setting of fault resistance for both phase-to-earth
RFPE
and phase-
to-phase
RFPP
should be as high as possible without interfering with the load
impedance in order to obtain reliable fault detection. However for zone1 it is
necessary to limit the reach according to setting instructions in order to avoid
overreach.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
225
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...