The logic can be controlled either by the autorecloser (zone extension) or by the
loss-of-load current (loss-of-load acceleration).
The loss-of-load acceleration gives selected overreach zone permission to operate
instantaneously after checking the loss-of-load condition. It can not operate for
three-phase faults.
16.5.3
Setting guidelines
M13854-4 v4
The parameters for the local acceleration logic functions are set via the local HMI
or PCM600.
Set
ZoneExtension
to
On
when the first trip from selected overreaching zone shall
be instantaneous and the definitive trip after autoreclosure a normal time-delayed
trip.
Set
LossOfLoad
to
On
when the acceleration shall be controlled by loss-of-load in
healthy phase(s).
LoadCurr
must be set below the current that will flow on the healthy phase when
one or two of the other phases are faulty and the breaker has opened at remote end.
Calculate the setting according to equation
.
min
0.5
Load
Base
I
LoadCurr
I
×
=
EQUATION1320 V1 EN-US
(Equation 534)
where:
ILoadmin is the minimum load current on the line during normal operation conditions.
The timer
tLoadOn
is used to increase the security of the loss-of-load function for
example to avoid unwanted release due to transient inrush current when energizing
the line power transformer. The loss-of-load function will be released after the
timer
tLoadOn
has elapsed at the same time as the load current in all three phases
are above the setting
LoadCurr
. In normal acceleration applications there is no
need for delaying the release, so set the
tLoadOn
to zero.
The drop-out timer
tLoadOff
is used to determine the window for the current
release conditions for Loss-of-load. The timer is by default set to 300ms, which is
judged to be enough to secure the current release.
The setting of the minimum current detector,
MinCurr
, should be set higher than
the unsymmetrical current that might flow on the non faulty line, when the breaker
at remote end has opened. At the same time it should be set below the minimum
load current transfer during normal operations that the line can be subjected to. By
default,
MinCurr
is set to 5% of
IBase
.
1MRK 506 369-UEN B
Section 16
Scheme communication
Line distance protection REL670 2.2 IEC
721
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...