A safety margin of 5% for the maximum static inaccuracy and a safety margin of
5% for maximum possible transient overreach have to be introduced. An additional
20% is suggested due to inaccuracy of instrument transformers under transient
conditions and inaccuracy in the system data.
The minimum primary current setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION285 V3 EN-US
(Equation 456)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel
line, as shown in Figure
, should be calculated.
IEC09000025-1-en.vsd
~
~
Z
A
Z
B
Z
L1
A
B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
IEC09000025 V1 EN-US
Figure 260:
Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in
M A X I
fA
I
fB
I
M
,
,
(
)
³
EQUATION287 V1 EN-US
(Equation 457)
Where:
I
fA
and I
fB
have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION288 V3 EN-US
(Equation 458)
The IED setting value
IN>>
is given in percent of the primary base current value,
IBase. The value for
IN>>
is given by the formula:
1MRK 506 369-UEN B
Section 9
Current protection
Line distance protection REL670 2.2 IEC
473
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...