![ABB REL670 2.2 IEC Applications Manual Download Page 324](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789324.webp)
R
X
IEC08000437.vsd
IEC08000437 V1 EN-US
Figure 162:
Rotation of load characteristic for a fault between two phases
This rotation may seem a bit awkward, but there is a gain in selectivity by using the
same measurement as for the quadrilateral characteristic since not all phase-to-
phase loops will be fully affected by a fault between two phases. It should also
provide better fault resistive coverage in quadrant 1. The relative loss of fault
resistive coverage in quadrant 4 should not be a problem even for applications on
series compensated lines.
8.10.3
Load encroachment characteristics
GUID-DD9A62C3-A56D-411B-8303-6F7BC4C6092D v1
The phase selector must at least cover the overreaching zone 2 in order to achieve
correct phase selection for utilizing single-phase autoreclosing for faults on the
entire line. It is not necessary to cover all distance protection zones. A safety
margin of at least 10% is recommended. In order to get operation from distance
zones, the phase selection output STCNDZ or STCNDLE must be connected to
input STCND on distance zones.
For normal overhead lines, the angle for the loop impedance φ for phase-to-earth
fault defined according to equation
Section 8
1MRK 506 369-UEN B
Impedance protection
318
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...