Short circuit power from the external network without infeed from the protected
line: 5000 MVA (assumed to a pure reactance).
We have all phase voltages and phase currents available and fed to the protection
IED. Therefore it is recommended to set the
MeasureMode
to positive sequence.
The impedance settings are set in pu with ZBase as reference:
2
2
20
2.0
200
UBase
ZBase
ohm
SBase
=
=
=
EQUATION1969 V1 EN-US
(Equation 434)
2
2
20
20
(
)
(
)
0.15
0.38
200
5000
ZA Z transf
Zsc network
j
j
j
ohm
=
+
=
×
+
=
EQUATION1970 V1 EN-US
(Equation 435)
This corresponds to:
0.38
0.19
0.19 90
2.0
j
ZA
j
pu
pu
=
=
=
Ð °
EQUATION1971 V1 EN-US
(Equation 436)
Set ZA to 0.19
2
20
'
0.25
0.5
200
d
ZB
jX
j
j
ohm
=
=
×
=
EQUATION1972 V2 EN-US
(Equation 437)
This corresponds to:
0.5
0.25
0.25 90
2.0
j
ZB
j
pu
pu
=
=
=
Ð °
EQUATION1973 V1 EN-US
(Equation 438)
Set ZB to 0.25
2
20
0.15
0.3
200
T
ZC
jX
j
j
ohm
=
=
×
=
EQUATION1974 V1 EN-US
(Equation 439)
This corresponds to:
0.3
0.15
0.15 90
2.0
j
ZC
j
pu
pu
=
=
=
Ð
o
EQUATION1975 V2 EN-US
(Equation 440)
Section 8
1MRK 506 369-UEN B
Impedance protection
434
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...