Table 13:
Trip LED (red)
LED state
Description
Off
Normal operation.
On
A protection function has tripped. An indication message is displayed if
the auto-indication feature is enabled in the local HMI.
The trip indication is latching and must be reset via communication, LHMI
or binary input on the LEDGEN component. To open the reset menu on
the LHMI, press
.
Flasing
Configuration mode.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An
individual alarm/status signal, connected to any of the LED function blocks, can be
assigned to one of the three LED colors when configuring the IED.
Table 14:
Alarm indications
LED state
Description
Off
Normal operation. All activation signals are off.
On
•
Follow-S sequence: The activation signal is on.
•
LatchedColl-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
•
LatchedAck-F-S sequence: The indication has been acknowledged, but the
activation signal is still on.
•
LatchedAck-S-F sequence: The activation signal is on, or it is off but the
indication has not been acknowledged.
•
LatchedReset-S sequence: The activation signal is on, or it is off but the
indication has not been acknowledged.
Flashing
•
Follow-F sequence: The activation signal is on.
•
LatchedAck-F-S sequence: The activation signal is on, or it is off but the
indication has not been acknowledged.
•
LatchedAck-S-F sequence: The indication has been acknowledged, but the
activation signal is still on.
5.4.2
Parameter management
GUID-5EE466E3-932B-4311-9FE1-76ECD8D6E245 v9
The LHMI is used to access the relay parameters. Three types of parameters can be
read and written.
•
Numerical values
•
String values
•
Enumerated values
Numerical values are presented either in integer or in decimal format with
minimum and maximum values. Character strings can be edited character by
character. Enumerated values have a predefined set of selectable values.
Section 5
1MRK 506 369-UEN B
Local HMI
102
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...