) 100
s
IN
I
IBase
IECEQUATION17003 V1 EN-US
(Equation 459)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (
IBase
).
Operation
: set the protection to
On
or
Off
.
IN>>
: Set operate current in % of
IB
.
IN>>Max
and
IN>>Min
should only be changed if remote setting of operation
current level,
IN>>
, is used. The limits are used for decreasing the used range of
the
IN>>
setting. If
IN>>
is set outside
IN>>Max
and
IN>>Min
, the closest of the
limits to
IN>>
is used by the function. If
IN>>Max
is smaller than
IN>>Min
, the
limits are swapped.
StValMult
: The set operate current can be changed by activation of the binary input
ENMULT to the set factor
StValMult
.
9.4
Directional residual overcurrent protection, four
steps EF4PTOC
IP14509-1 v8
9.4.1
Identification
M14881-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent
protection, four steps
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
51N_67N
9.4.2
Application
M12509-12 v10
The directional residual overcurrent protection, four steps EF4PTOC is used in
several applications in the power system. Some applications are:
Section 9
1MRK 506 369-UEN B
Current protection
474
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...