SEMOD168232-268 v2
A
B
Z<
Z<
Z<
C
T
I
C
I
A
I
B
-I
B
en05000224.vsd
DOCUMENT11524-IMG869 V1 EN-US
Figure 65:
Example of tapped line with Auto transformer
This application gives rise to similar problem that was highlighted in section
that is, increased measured impedance due to fault current
infeed. For example, for faults between the T point and B station the measured
impedance at A and C is as follows:
Z
A
=Z
AT
+ ·Z
TF
I
A
+ I
C
I
A
DOCUMENT11524-IMG3509 V3 EN-US
(Equation 42)
Z
Z
Z
I
I
I
Z
U
U
C
Trf
CT
A
C
C
TF
=
+
+
+
⋅
⋅
2
1
2
DOCUMENT11524-IMG3510 V3 EN-US
(Equation 43)
Where:
ZAT and ZCT
is the line impedance from the B respective C station to the T point.
IA and IC
is fault current from A respective C station for fault between T and B.
U2/U1
Transformation ratio for transformation of impedance at U1 side of the transformer to
the measuring side U2 (it is assumed that current and voltage distance function is
taken from U2 side of the transformer).
Section 8
1MRK 506 369-UEN B
Impedance protection
160
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...