18.3
Liquid medium supervision SSIML
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
18.3.1
Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation liquid monitoring function
SSIML
-
71
18.3.2
Application
GUID-140AA10C-4E93-4C23-AD57-895FADB0DB29 v7
Liquid medium supervision (SSIML) is used for monitoring the oil insulated
device condition. For example, transformers, shunt reactors, and so on. When the
level becomes too low compared to the required value, the operation is blocked to
minimize the risk of internal failures. Binary information based on the oil level in
the oil insulated devices are used as input signals to the function. In addition, the
function generates alarms based on the received information.
18.3.3
Setting guidelines
GUID-0C8E498B-2A65-44ED-91D6-53EC72F49222 v4
The parameters for Liquid medium supervision SSIML can be set via local HMI or
Protection and Control Manager PCM600.
Operation
: This is used to disable/enable the operation of liquid medium
supervision i.e.
Off
/
On
.
LevelAlmLimit
: This is used to set the limit for a level alarm condition in the oil
insulated device.
LevelLOLimit
: This is used to set the limit for a level lockout condition in the oil
insulated device.
TempAlarmLimit
: This is used to set the limit for a temperature alarm condition in
the oil insulated device.
TempLOLimit
: This is used to set the limit for a temperature lockout condition in
the oil insulated device.
tLevelAlarm
: This is used to set the time delay for a level alarm indication, given in
s.
tLevelLockOut
: This is used to set the time delay for a level lockout indication,
given in s.
tTempAlarm
: This is used to set the time delay for a temperature alarm indication,
given in s.
1MRK 506 369-UEN B
Section 18
Monitoring
Line distance protection REL670 2.2 IEC
777
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...