The
ImpedanceZC
is the forward impedance giving the borderline between zone 1
and zone 2. ZC should be equal to the transformer reactance ZT. The impedance is
given in % of the base impedance, see equation
The angle of the impedance line ZB – ZA is given as
AnglePhi
in degrees. This
angle is normally close to 90°.
StartAngle
: An alarm is given when movement of the rotor is detected and the rotor
angle exceeds the angle set for
StartAngle
. The default value 110° is recommended.
It should be checked so that the points in the impedance plane, corresponding to
the chosen
StartAngle
does not interfere with apparent impedance at maximum
generator load.
TripAngle
: If a pole slip has been detected: change of rotor angle corresponding to
slip frequency 0.2 – 8 Hz, the slip line ZA – ZB is crossed and the direction of
rotation is the same as at start, a trip is given when the rotor angle gets below the
set
TripAngle
. The default value 90° is recommended.
N1Limit
: The setting
N1Limit
gives the number of pole slips that should occur
before trip, if the crossing of the slip line ZA – ZB is within zone 1, that is, the
node of the pole slip is within the generator transformer block. The default value 1
is recommended to minimize the stress on the generator and turbine at out of step
conditions.
N2Limit
: The setting
N2Limit
gives the number of pole slips that should occur
before trip, if the crossing of the slip line ZA – ZB is within zone 2, that is, the
node of the pole slip is in the external network. The default value 3 is
recommended give external protections possibility to split the network and thus
limit the system consequencies.
ResetTime
: The setting
ResetTime
gives the time for (PSPPPAM) function to reset
after start when no pole slip been detected. The default value 5s is recommended.
8.16.3.1
Setting example for line application
SEMOD172162-25 v3
In case of out of step conditions this shall be detected and the line between
substation 1 and 2 shall be tripped.
IED
ZB
Line impedance = ZC
ZA = forward source impedance
IEC07000014_2_en.vsd
IEC07000014 V2 EN-US
Figure 233:
Line application of pole slip protection
If the apparent impedance crosses the impedance line ZB – ZA this is the detection
criterion of out of step conditions, see figure
.
Section 8
1MRK 506 369-UEN B
Impedance protection
428
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...