Busbar
Protection
Busbar
1
2
2
1
en06000196.vsd
IED
1
IEC06000196 V2 EN-US
Figure 11:
Example how to set CTStarPoint parameters in the IED
For busbar protection, it is possible to set the
CTStarPoint
parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in Figure
, set
CTStarPoint
=
ToObject
, and for all CT
inputs marked with 2 in Figure
, set
CTStarPoint
=
FromObject
.
The second solution will be to use all connected bays as reference objects. In that
case for all CT inputs marked with 1 in Figure
, set
CTStarPoint
=
FromObject
,
and for all CT inputs marked with 2 in Figure
, set
CTStarPoint
=
ToObject
.
Regardless which one of the above two options is selected, busbar differential
protection will behave correctly.
1MRK 506 369-UEN B
Section 4
Analog inputs
Line distance protection REL670 2.2 IEC
71
Application manual