based on phase-to-phase current variation. The main application is as one of local
criterion to increase security when transfer trips are used.
16.8.5.3
Setting guidelines
GUID-00CE5289-3789-437D-A9AE-8E4BDD7C9D8A v2
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
I>
: Level of fixed threshold given in % of
IBase
. This setting should be based on
fault calculations to find the current increase in case of a fault at the most remote
point where the direct trip scheme shall be active. The phase to phase current shall
be calculated for different types of faults (single phase to earth, phase to phase to
earth, phase to phase and three phase short circuits) at different switching states in
the network. In case of switching of large objects (shunt capacitor banks,
transformers, etc.) large change in current can occur. The
I>
setting should be
larger than estimated switch in currents measured by the protection.
tHold
: Hold time (minimum signal duration). This time setting shall be long
enough to assure that the CR-signal is received. The default value
0.5
s is
recommended.
tDelay
: Trip time is set according to the individual application.
16.8.6
Carrier receive logic LCCRPTRC
GUID-13BF45AF-B04C-4C6D-B59D-79A51241C449 v1
16.8.6.1
Identification
GUID-D420E532-37DC-442F-B847-8F73EE8527A7 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Carrier receive logic
LCCRPTRC
-
94
16.8.6.2
Application
GUID-2CAA361A-C3A9-44F0-99DF-FB4E4FA227E3 v1
In the Direct transfer trip scheme, the received CR signal gives the trip to the
circuit breaker after checking certain local criteria functions in order to increase the
security of the overall tripping functionality. Carrier receive logic (LCCRPTRC)
checks for the CR signals and passes the local check trip to the circuit breaker.
LCCRPTRC receives the two CR signals, local criterion trip signals and releases
the trip to the circuit breaker based on the input signal status and mode of
operation. There are two modes of operation in CR channel logic. In the case of '1
out of 2' mode if any one of the two CR is received then the trip signal coming
from the local criterion is released, and in case of '2 out of 2' mode both the CR’s
Section 16
1MRK 506 369-UEN B
Scheme communication
734
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...