The residual power, measured by the sensitive earth fault protections in A and B
will be:
0 A
0 A
0
S
3U
3I
=
×
EQUATION1951 V1 EN-US
(Equation 476)
0 B
0 B
0
S
3U
3I
=
×
EQUATION1952 V1 EN-US
(Equation 477)
The residual power is a complex quantity. The protection will have a maximum
sensitivity in the characteristic angle RCA. The apparent residual power
component in the characteristic angle, measured by the protection, can be written:
0 A ,prot
0 A
0
A
S
3U
3I cos
j
=
×
×
EQUATION1953 V1 EN-US
(Equation 478)
0 B,prot
0 B
0
B
S
3U
3I cos
j
=
×
×
EQUATION1954 V1 EN-US
(Equation 479)
The angles φ
A
and φ
B
are the phase angles between the residual current and the
residual voltage in the station compensated with the characteristic angle RCA.
The protection will use the power components in the characteristic angle direction
for measurement, and as base for the inverse time delay.
The inverse time delay is defined as:
0
0
inv
0
0
kSN (3I 3U cos (reference))
t
3I 3U cos (measured)
×
×
×
j
=
×
×
j
EQUATION1942 V2 EN-US
(Equation 480)
The function can be set
On/Off
with the setting of
Operation
.
Common base IED values for primary current (IBase), primary voltage (UBase)
and primary power (SBase) are set in a Global base values for settings function
GBASVAL.
GlobalBaseSel
: It is used to select a GBASVAL function for reference of base
values.
RotResU
: It is a setting for rotating the polarizing quantity ( 3U
0
) by 0 or 180
degrees. This parameter is set to 180 degrees by default in order to inverse the
residual voltage ( 3U
0
) to calculate the reference voltage (-3U
0
e
-jRCADir
). Since the
reference voltage is used as the polarizing quantity for directionality, it is important
to set this parameter correctly.
With the setting
OpMode
the principle of directional function is chosen.
Section 9
1MRK 506 369-UEN B
Current protection
500
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...