Set
Unblock
=
Off
(Set to
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
= 0.035 s
Set
DeltaI
= 10 %IB
Set
DeltaU
= 5 %UB
Set
Delta3I0
= 10 %IB
Set
Delta3U0
= 5 %UB
16.1.3.3
Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
On
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
16.1.3.4
Permissive overreaching scheme
M13869-34 v4
Set
Operation
=
On
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
16.1.3.5
Unblocking scheme
M13869-43 v4
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
Set
tSecurity
= 0.035 s
16.1.3.6
Intertrip scheme
M13869-62 v5
Set
Operation
=
On
Set
SchemeType
=
Intertrip
Set
tCoord
= 50 ms (10 ms + maximal transmission time)
Table continues on next page
Section 16
1MRK 506 369-UEN B
Scheme communication
708
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...