![ABB REL670 2.2 IEC Applications Manual Download Page 465](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789465.webp)
IEC09000025-1-en.vsd
~
~
Z
A
Z
B
Z
L1
A
B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
IEC09000025 V1 EN-US
Figure 252:
Two parallel lines. Influence from parallel line to the through fault
current: I
M
The minimum theoretical current setting for the overcurrent protection function
(Imin) will be:
Imin MAX I
fA
I
fB
I
M
,
,
(
)
³
EQUATION82 V1 EN-US
(Equation 446)
Where I
fA
and I
fB
have been described in the previous paragraph. Considering the
safety margins mentioned previously, the minimum setting (Is) for the
instantaneous phase overcurrent protection 3-phase output is then:
Is
³
1.3·Imin
EQUATION83 V2 EN-US
(Equation 447)
The protection function can be used for the specific application only if this setting
value is equal or less than the maximum phase fault current that the IED has to
clear.
The IED setting value
IP>>
is given in percentage of the primary base current
value,
IBase
. The value for
IP>>
is given from this formula:
100
Is
IP
IBase
>>=
×
EQUATION1147 V3 EN-US
(Equation 448)
1MRK 506 369-UEN B
Section 9
Current protection
Line distance protection REL670 2.2 IEC
459
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...