Set
tDelayRev
timer at the maximum reset time for the communication equipment
that gives the carrier receive (CRLx) signal plus 30 ms. A minimum setting of
40
ms
is recommended, typical
60 ms
.
A long
tDelayRev
setting increases security against unwanted tripping, but delay
the fault clearing in case of a fault developing from one line to involve the other
one. The probability of this type of fault is small. Therefore set
tDelayRev
with a
good margin.
Set the pick-up delay
tPickUpRev
to <80% of the minimum sum of breaker operate
time + communication delay time, but with a minimum of
20 ms
.
Weak-end infeed logic
Set
OperationWEI
to
Echo
, to activate the weak-end infeed function with only
echo function.
Set
OperationWEI
to
Echo&Trip
to obtain echo with trip.
Set
tPickUpWEI
to
10 ms
, a short delay is recommended to avoid that spurious
carrier received signals will activate WEI and cause unwanted communications.
Set the voltage criterion
UPP<
and
UPE<
for the weak-end trip to
70
% of the
system base voltage
UBase
. The setting should be below the minimum operate
voltage of the system but above the voltage that occurs for fault on the protected
line. The phase-to-phase elements must be verified to not operate for phase to earth
faults.
When single phase tripping is required a detailed study of the
voltages at phase-to-phase respectively phase-to-earth faults, at
different fault locations, is normally required.
16.5
Local acceleration logic ZCLCPSCH
SEMOD52894-1 v4
16.5.1
Identification
M14860-1 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local acceleration logic
ZCLCPSCH
-
-
16.5.2
Application
M13821-3 v4
The local acceleration logic (ZCLCPSCH) is used in applications where a
conventional teleprotection scheme is not available (no communication channel),
but where the user still requires fast clearance for faults on the whole line.
Section 16
1MRK 506 369-UEN B
Scheme communication
720
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...