Simplified, the example can be shown as a triangle, see figure
ZA
ZB
Zload
R
X
en07000016.vsd
IEC07000016 V1 EN-US
Figure 235:
Simplified figure to derive StartAngle
0
0
32
52
arctan
arctan
arctan
+ arctan
= 21.8 + 33.0 55
80
80
³
=
»
ZB
ZA
angleStart
+
Zload
Zload
EQUATION1968 V2 EN-US
(Equation 433)
In case of minor damped oscillations at normal operation we do not want the
protection to start. Therefore we set the start angle with large margin.
Set
StartAngle
to 110°
For the
TripAngle
it is recommended to set this parameter to 90° to assure limited
stress for the circuit breaker.
In a power system it is desirable to split the system into predefined parts in case of
pole slip. The protection is therefore situated at lines where this predefined split
shall take place.
Normally the
N1Limit
is set to 1 so that the line will be tripped at the first pole slip.
If the line shall be tripped at all pole slip situations also the parameter
N2Limit
is
set to 1. In other cases a larger number is recommended.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
431
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...