PhasorXReport
: Enables/Disables the phasor channel X (reporting of
PhasorX) by choosing
On
/
Off
setting.
•
PhasorX
: The group selector for PhasorX. Here, the user can select the
type of reported synchrophasor from the phasor channel X as either a 3-
phase symmetrical component or a single-phase phasor. The options are
as follows:
•
A
•
B
•
C
•
NEGSEQ
•
POSSEQ
•
ZEROSEQ
•
PhasorXUseFreqSrc
: Enables/Disables the contribution of Phasor
channel X in automatic frequency source selection by choosing
On
/
Off
setting. Each voltage-connected preprocessor block delivers the
frequency data, derived from the analog input AC voltage values, to the
respective voltage phasor channel. Every phasor channel has a user-
settable parameter (
PhasorXUseFreqSrc
) to be used as a source of
frequency data for reporting to the PDC client. It is very important to set
this parameter to
On
for the voltage-connected phasor channels. There is
an automatic frequency source selection logic to ensure an uninterrupted
reporting of the system frequency to the PDC client. More information is
available under the section
3. ANALOGREPORT is the function block responsible for reporting the analog
values. Each instance of ANALOGREPORT function block has 24 analog
channels with the following setting parameters; where X is a number from 1 to
24:
•
AnalogXRange
: This parameter defines a range between
-AnalogXRange
and
+AnalogXRange
for AnalogX value. The range will be used by the
IED to apply a proper scale factor to the AnalogX values when
Integer
format is used. It refers to the 4-byte ANUNIT field of the configuration
frames 1, 2 organization and the 8-byte ANSCALE field of the
configuration frame 3 organization defined in IEEE C37.118.2 message
format. The
AnalogXRange
value can be a number between
3277.0
and
10000000000
. This setting is only important if the AnalogDataType
setting is selected as
Integer
. More information is available under the
Scaling Factors for ANALOGREPORT channels
.
•
AnalogXUnitType
: Unit type for analog signal X. It refers to the 4-byte
ANUNIT field of the configuration frames 1, 2 organization defined in
IEEE C37.118.2 message format. The options are
Single point-on-wave
,
RMS of analog input
and
Peak of analog input
.
Section 6
1MRK 506 369-UEN B
Wide area measurement system
128
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...