![ABB REL670 2.2 IEC Applications Manual Download Page 837](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789837.webp)
IED
IED
IED
Substation LAN
IEC05000715-4-en.vsd
Remote
monitoring
Utility LAN
WAN
IEC05000715 V4 EN-US
Figure 418:
SPA communication structure for a remote monitoring system via a
substation LAN, WAN and utility LAN
SPA communication is mainly used for the Station Monitoring System. It can
include different IEDs with remote communication possibilities. Connection to a
PC can be made directly (if the PC is located in the substation), via a telephone
modem through a telephone network with ITU (former CCITT) characteristics or
via a LAN/WAN connection.
glass
<1000 m according to optical budget
plastic
<25 m (inside cubicle) according to optical budget
Functionality
SEMOD115767-25 v3
The SPA protocol V2.5 is an ASCII-based protocol for serial communication. The
communication is based on a master-slave principle, where the IED is a slave and
the PC is the master. Only one master can be applied on each fiber optic loop. A
program is required in the master computer for interpretation of the SPA-bus codes
and for translation of the data that should be sent to the IED.
For the specification of the SPA protocol V2.5, refer to SPA-bus Communication
Protocol V2.5.
21.5.2
Setting guidelines
M11876-3 v7
SPA, IEC 60870-5-103 and DNP3 use the same rear communication port. This port
can be set for SPA use on the local HMI under
Main menu /Configuration /
Communication /Station communication/Port configuration/SLM optical
serial port/PROTOCOL:1
. When the communication protocol is selected, the
IED is automatically restarted, and the port then operates as a SPA port.
The SPA communication setting parameters are set on the local HMI under
Main
menu/Configuration/Communication/Station communication/SPA/SPA:1
.
1MRK 506 369-UEN B
Section 21
Station communication
Line distance protection REL670 2.2 IEC
831
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...