ARMode
=
1/2/3ph
, is done from a hardware function key at the front of the IED, but
alternatively there can for example, be a physical selector switch on the front of the
panel which is connected to a binary to integer function block (BTIGAPC).
The connection example for selection of the auto reclosing mode is shown in
Figure
.
IEC14000040-1-en.vsd
IEC07000119 V3 EN-US
Figure 306:
Selection of the auto-reclose mode from a hardware functional key
in front of the IED
15.2.2.15
Auto reclosing reclaim timer
M12391-202 v4
The
tReclaim
timer defines the time it takes from issue of the breaker closing
command, until the auto recloser resets. Should a new trip occur during this time, it
is treated as a continuation of the first fault. The reclaim timer is started when the
circuit breaker closing command is given.
15.2.2.16
Pulsing of the circuit breaker closing command and counter
M12391-205 v4
The circuit breaker closing command,
CLOSECB
is given as a pulse with a
duration set by the
tPulse
setting. For circuit breakers without an anti-pumping
function, close pulse cutting can be used. It is selected by the
CutPulse
setting. In
case of a new start pulse (trip), the breaker closing command pulse is then cut
(interrupted). The minimum breaker closing command pulse length is always
50ms. At the issue of the breaker closing command, the appropriate auto recloser
operation counter is incremented. There is a counter for each type of auto reclosing
command and one for the total number of auto reclosing commands.
15.2.2.17
Transient fault
M12391-208 v4
After the breaker closing command the reclaim timer keeps running for the set
tReclaim
time. If no start (trip) occurs within this time, the auto recloser will reset.
The circuit breaker remains closed and the operating gear recharges. The
CBCLOSED
and
CBREADY
input signals will be set.
15.2.2.18
Permanent fault and reclosing unsuccessful signal
M12391-211 v5
If a new start occurs, and the number of auto reclosing shots is set to 1, and a new
START
or
TRSOTF
input signal appears, after the circuit breaker closing command,
the
UNSUCCL
output (unsuccessful reclosing) is set high. The timer for the first
Section 15
1MRK 506 369-UEN B
Control
622
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...