Section 11
Frequency protection
11.1
Underfrequency protection SAPTUF
IP15746-1 v3
11.1.1
Identification
M14865-1 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Underfrequency protection
SAPTUF
f <
SYMBOL-P V1 EN-US
81
11.1.2
Application
M13350-3 v4
Underfrequency protection SAPTUF is applicable in all situations, where reliable
detection of low fundamental power system frequency is needed. The power
system frequency, and the rate of change of frequency, is a measure of the
unbalance between the actual generation and the load demand. Low fundamental
frequency in a power system indicates that the available generation is too low to
fully supply the power demanded by the load connected to the power grid.
SAPTUF detects such situations and provides an output signal, suitable for load
shedding, generator boosting, HVDC-set-point change, gas turbine start up and so
on. Sometimes shunt reactors are automatically switched in due to low frequency,
in order to reduce the power system voltage and hence also reduce the voltage
dependent part of the load.
SAPTUF is very sensitive and accurate and is used to alert operators that frequency
has slightly deviated from the set-point, and that manual actions might be enough.
The underfrequency signal is also used for overexcitation detection. This is
especially important for generator step-up transformers, which might be connected
to the generator but disconnected from the grid, during a roll-out sequence. If the
generator is still energized, the system will experience overexcitation, due to the
low frequency.
11.1.3
Setting guidelines
M13355-3 v8
All the frequency and voltage magnitude conditions in the system where SAPTUF
performs its functions should be considered. The same also applies to the
associated equipment, its frequency and time characteristic.
1MRK 506 369-UEN B
Section 11
Frequency protection
Line distance protection REL670 2.2 IEC
559
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...