operation of compensated over and under voltage function without corresponding
transfer trip received from remote end.
Switchable shunt reactors located on both line terminals and substation bus-bars
are commonly used on long radial EHV transmission networks for the purpose of
voltage control during daily/seasonal load variations.
The function can internally correct for the current through the local shunt reactor.
The setting
EnShuntReactor
should be
On
if there is a shunt reactor on the line.
Change in this setting will be effected only when IED is restarted. Hence this
setting should be configured during installing and then connection and
disconnection of shunt reactor breaker should be handled by the input SWIPOS. In
figure
, if the measured current I
S
is configured in the IED, then internal shunt
reactor correction should be used (The setting
EnShuntReactor
should be
On
if
there is a shunt reactor on the line. Change in this setting will reboot the IED to
take effect of X
SR
. Hence this setting should be configured during installing and
then connection and disconnection of shunt reactor breaker should be handled by
the input SWIPOS). Also, for shunt reactor connected through the breaker or
disconnector, status of the same must be configured in the IED as shown in figure
Frequently, the input current to the line protection IED is already corrected for the
current through the local shunt reactor. In figure
if the measured current I
L
is
connected to the IED then even if local shunt reactor is present its correction
should not be done inside the function, otherwise this will result into incorrect
calculation for compensated voltage.
R
L
I
s
I
L
U
s
U
R
I
R
X
SR
IED
Breaker Status
IEC09000775-1-en.vsd
IEC09000775 V1 EN-US
Figure 381:
Breaker status configured with IED
16.8.4.3
Setting guidelines
GUID-DE3963D6-016E-41AD-832F-1D10DD26AABA v2
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
OperationUV
: Used to set the under-voltage function
On
or
Off
.
Section 16
1MRK 506 369-UEN B
Scheme communication
732
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...