The setting values of all parameters that belong to ZMHPDIS must correspond to
the parameters of the protected line and be coordinated to the selectivity plan for
the network.
Use different setting groups for the cases when the parallel line is in operation, out
of service and not earthed and out of service and earthed in both ends. In this way it
is possible to optimize the settings for each system condition.
Appropriate selection of zero sequence compensation factor
KNMagx
and
KNAngx
(where x=1-5) when parallel line can be in service, out of service, or out of service
and earthed at both ends.
When Directional impedance element for mho characteristic
(ZDMRDIR) is used together with Fullscheme distance protection,
mho characteristic (ZMHPDIS) the following settings for parameter
DirEvalType
in ZDMRDIR is vital:
•
alternative
Comparator
is strongly recommended
•
alternative
Imp/Comp
should generally not be used
•
alternative Impedance should not be used. This alternative is
intended for use together with Distance protection zone,
quadrilateral characteristic (ZMQPDIS)
8.4.3.2
Setting of zone 1
GUID-4A9FE32F-DA27-401A-ADA1-94060A9F6C76 v1
The zone 1 distance elements must be set to underreach a protected circuit to
ensure external fault security.
The different errors mentioned earlier usually require a limitation of the
underreaching zone (normally zone 1) to 75 - 90% of the protected line.
In case of parallel lines, consider the influence of the mutual coupling according to
section “Setting of zones for parallel line application” and select the case(s) /
options that are valid in the particular application.
By proper setting it is possible to compensate for the cases when the parallel line is
in operation, out of service and not earthed and out of service and earthed in both
ends.
8.4.3.3
Setting of overreaching zone
8.4.3.4
Setting of zone 2
GUID-5A41709F-8AB2-4A4B-9B3E-3B48EBD0DE0D v1
Zone 2 distance elements must be set according to the following criteria:
Section 8
1MRK 506 369-UEN B
Impedance protection
250
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...