8.2.3.2
Resistive reach with load encroachment characteristic
M13142-312 v4
The procedure for calculating the settings for the load encroachment consist
basically to define the load angle
ArgLd
, the blinder
RLdFw
in forward direction
and blinder
RLdRv
in reverse direction, as shown in figure
R
X
RLdFw
RLdRv
ArgLd
ArgLd
ArgLd
ArgLd
IEC09000050-1-en.vsd
IEC09000050 V1 EN-US
Figure 106:
Load encroachment characteristic
The load angle
ArgLd
is the same in forward and reverse direction, so it could be
suitable to begin to calculate the setting for that parameter. Set the parameter to the
maximum possible load angle at maximum active load. A value bigger than 20°
must be used.
The blinder in forward direction,
RLdFw
, can be calculated according to
2
min
0.8
exp max
U
RLdFw
P
=
×
where:
Pexp max is the maximum exporting active power
Umin
is the minimum voltage for which the Pexp max occurs
0.8
is a security factor to ensure that the setting of
RLdFw can be lesser than the calculated
minimal resistive load.
The resistive boundary
RLdRv
for load encroachment characteristic in reverse
direction can be calculated in the same way as
RLdFw
, but use maximum
importing power that might occur instead of maximum exporting power and the
relevant Umin voltage for this condition.
Section 8
1MRK 506 369-UEN B
Impedance protection
208
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...