Verification and validation 475
Validation of the SLS functions
Note:
STO and SSE validation test must always be done before SLS or any other
validation tests.
Follow these steps to validate all SLS functions (SLS1...4) that are used in the
application. SLS1 is used as an example later in this section.
Note:
If SLS4 limits are changed, this will have an impact on varSLS function also,
which means that both of these functions must be validated.
1. Make sure that the input for the SLS1 function is wired and configured according
to the wiring diagram.
2. Make sure that the SLS1 function is configured according to your design. For a
configuration example, see section
on page
. Check these
settings:
Activation:
•
•
•
(only for SLS1).
Functionality for the SLS function:
•
•
•
•
.
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality:
a) with ramp monitoring:
•
SLS activation monitoring method
= Ramp
•
•
•
•
•
•
drive parameter 23.23 emergency stop time, If
=
0 ms.
OR
b) with time monitoring:
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...