468 Verification and validation
Validation of the SBC function
SBC function always uses the drive STO.
Drive STO is always activated immediately in the following cases/situations:
• FSO STO function
• SSE, when it is configured to be immediate STO
• SSE ramp or SS1 function is completed.
Validation of the delayed brake function
1. Check the wiring between the FSO module and safe brake, and make sure that
they are done correctly according to the design.
2. Make sure that the SBC function is configured correctly according to your design.
For a configuration example, see section
How to configure the SBC in the STO
. Check these settings:
Functionality:
•
= Delayed brake
•
•
•
•
•
•
.
3. Check that the drive STO and the SBC are activated correctly based on your
application needs.
a) When positive STO SBC delay (
) is used: Check that the drive STO is
activated first and the SBC after the delay has elapsed.
Note:
When an encoder is used: If the zero speed limit (
) is reached
before the positive STO SBC delay (
has elapsed, the FSO module
activates the SBC immediately when the motor speed is below the zero speed
limit.
b) When
is 0 ms, Check that the drive STO is activated
at the same time as the SBC.
c) When negative STO SBC delay (
) is used: Check that the SBC is
activated first and the drive STO after the delay has elapsed.
4. Make sure that the required failure reaction (
) takes place if there is no
SBC feedback signal (
). For example, disconnect the SBC feedback
cable to verify.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...