![ABB FSO-21 User Manual Download Page 62](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728062.webp)
62 Safety functions
At power-up, the FSO goes into the Start-up mode. During the power-up process,
FSO is in Safe state (STO active). It performs start-up checks and, according to the
configuration, enters the Operational state either automatically or after an
acknowledgement request from the FSO I/O or from a safety PLC.
The Drive composer pro PC tool can request the Configuration mode, when the FSO
is in the Start-up, Operational, Safe or Fail-safe mode and the drive is in the Torque
off mode (not modulating). The FSO exits the Configuration mode into the Start-up
mode when the user either:
• downloads the new configuration to the FSO, or
• reboots the module
(for rebooting instructions, see chapter
on page
).
If there is an internal fault, the FSO enters the Fail-safe mode. To identify and recover
from the cause of the fault, see section
on page
The FSO exits the Fail-safe mode into the Start-up mode when the user reboots the
module (for rebooting instructions, see chapter
on page
).
When the FSO is in the Power down, Start-up, Configuration, Safe or Fail-safe mode,
the drive STO function is always active. When the FSO is in the Operational state, the
drive STO function is inactive (except when the POUS function is active, the drive
STO function is also active).
Note
: When the drive is connected to a safety PLC via the PROFIsafe over
PROFINET communication bus, see the states diagrams in section
on page
in chapter
.
Cascade
It is possible to cascade up to six FSO modules into a daisy-chain type network
(resembles somewhat an I/O master/follower system): If an FSO triggers a cascaded
safety function, it passes the triggering information to the next FSO, which triggers
the next one, and so on, until the last FSO again triggers the first one.
Without a PROFIsafe communication bus, you can cascade only safety functions
which have a primary and a secondary digital input: STO, SS1, SSE,SLS1, SDI
positive and SDI negative.
If you want to a cascade safety function which has only one digital input (SLS2,
SLS3, SLS4, SSM1, SSM2, SSM3, SSM4), you must have a PROFIsafe
communication bus and configure the safety function request from a safety PLC.
For detailed configuration instructions, see section
on page
.
This figure shows an example cascade configuration. Two different safety functions
are cascaded in the same cascaded system. Safety function 1 is cascaded in one
cascade loop (Cascade A) and safety function 2 in another (Cascade B).
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...