Fault tracing 495
AAA6 FSO SLS3 hit
FSO module detected an
SLS3 speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SLS is configured properly.
Make sure that SLS trip limits are
defined properly.
Check that mute time values are
defined properly (
if enabled, and
).
2) 6)
AAA7 FSO SLS4 hit
FSO module detected an
SLS4 speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SLS is configured properly.
Make sure that SLS trip limits are
defined properly.
Check that mute time values are
defined properly (
if enabled, and
).
2) 6)
AAA8 FSO SMS hit
FSO module detected an
SMS speed trip limit
violation.
Investigate the reason for trip from
the application point of view. If
application is OK, then make sure
that SMS is configured properly.
Make sure that SMS trip limits are
defined properly.
Check that mute time values are
defined properly (
if enabled).
2) 6)
AAA9 FSO SAR0 hit
FSO module detected an
SAR0 limit violation.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
AAAA FSO SAR1 hit
FSO module detected an
SAR1 limit violation.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
AAB0 FSO SDI positive
hit
SDI positive exceeded the
tolerance limit to the
forbidden direction.
Make sure that SDI tolerance values
are defined properly.
Check limits of the drive.For example,
see the usage of DC hold from the
drive firmware manual.
2)
Code
(hex)
Name
Cause
What to do
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...