Configuration 361
Configuring SAR
How to configure SARn
To configure the SARn (n = 0…1), set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter groups
page
on page
. See also section
on page
Example:
The figure below shows an example of a SAR1 monitoring set-up:
• SAR1
• ramp time from Scaling speed to zero: 1000 ms
200.112 SAR1 ramp time to zero
= 1000 ms
)
• Scaling speed: 1500 rpm (
1500 rpm
)
• initial range for monitoring: 100 ms (
100 ms
)
• minimum allowed ramp time: 500 ms
500 ms
)
• maximum allowed ramp time: 1000 ms
=
1500 ms
).
Note:
If you use SAR1 in several safety functions at the same time, tune it according
to the function which requires the tightest monitoring range.
= 500 ms
= 1500 ms
200.112 =
1000 ms
= 1500 rpm
SAR1
Time
Speed
= 100 ms
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...