444 Parameters
SAFEIO.24 Safety relay 2 output Sets the digital output for safety relay 2.
.
Note
: The output must always be redundant.
Otherwise the feedback signal of the safety
relay is not used (see
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
SAFEIO.25 Safety relay 2
feedback
Sets the digital feedback input of safety
relay 2.
Parameter
sets the type of the feedback
input.
None
No input connected
DI X113:1
Single input X113:1
DI X113:2
Single input X113:2
DI X113:3
Single input X113:3
DI X113:4
Single input X113:4
DI X114:1
Single input X114:1
DI X114:2
Single input X114:2
DI X114:3
Single input X114:3
DI X114:4
Single input X114:4
SAFEIO.26 Safety relay 2
feedback type
Sets the type of the feedback signal for
safety relay 2.
Note
: The feedback delay is 800 ms for both
feedback types, that is, a feedback signal
from the safety relay must be received within
800 ms.
Mechanicall
y linked NC
contacts
Mechanically linked
NC contacts
Feedback of the safety relay is NC (inverted
state compared with the relay).
Mechanically linked
NO contacts
Feedback of the safety relay is NO (same
state compared with the relay).
SAFEIO.31 DI diagnostic pulse
length
Sets the length of the diagnostic pulse for
digital inputs.
0.5 ms
Length of the diagnostic pulse is 0.5 ms.
1 ms
Length of the diagnostic pulse is 1 ms.
2 ms
Length of the diagnostic pulse is 2 ms.
SAFEIO.32 DI diagnostic pulse
period
Sets the time during which the FSO module
must receive at least one whole diagnostic
pulse.
10,000 ms
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...