PROFIsafe 257
18. Set F-Parameters of the FENA module:
•
In the hardware configuration, double-click
PROFIsafe ABB_PS1
to open the
Properties
window.
•
On the
PROFIsafe
tab, modify the F_Dest_Add and F_WD_Time values as
needed.
•
F_Source_Add is the address of the safety controller station. You can
modify this in the
host
F Parameters tab.
•
F_Dest_Add is the address of the FENA module. This is defined by FSO
parameter
, see section
Configuring the safety fieldbus
on page
These two define the codename for the PROFIsafe relationship of this
particular FENA module and the safety controller station.
•
F_WD_Time is the PROFIsafe watchdog time. See section
on page
for instructions on how to calculate the correct
watchdog time.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...