![ABB FSO-21 User Manual Download Page 436](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728436.webp)
436 Parameters
SSMx.04 SSM4 activity and
version
Activates or deactivates the SSM4 function
and shows the version of the SSM4 function.
Disabled
Deactivates the SSM4 function.
Version 1
Activates version 1 of the SSM4 function.
SSMx.11 SSM1 input
Sets the digital input connected to the SSM1
function.
None
No input connected
DI X113:1 & X114:1 Redundant input X113:1 & X114:1
DI X113:2 & X114:2 Redundant input X113:2 & X114:2
DI X113:3 & X114:3 Redundant input X113:3 & X114:3
DI X113:4 & X114:4 Redundant input X113:4 & X114:4
DI X113:1
Single input X113:1
DI X113:2
Single input X113:2
DI X113:3
Single input X113:3
DI X113:4
Single input X113:4
DI X114:1
Single input X114:1
DI X114:2
Single input X114:2
DI X114:3
Single input X114:3
DI X114:4
Single input X114:4
Always on
The SSM1 function is always on.
SSMx.12 SSM1 limit negative Sets the negative speed limit for the SSM1
function.
0.0 rpm
-35880.0 …0.0 rpm Speed
SSMx.13 SSM1 limit positive
Sets the positive speed limit for the SSM1
function.
0.0 rpm
0.0…35880.0 rpm
Speed
SSMx.14 SSM1 output
Sets the digital output connected to the
SSM1 function. Active when the motor
speed is within the SSM1 speed limits.
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
DO X113:8 & X114:8 Redundant output X113:8 & X114:8
DO X113:9 & X114:9 Redundant output X113:9 & X114:9
DO X113:7
Single output X113:7
DO X113:8
Single output X113:8
DO X113:9
Single output X113:9
DO X114:7
Single output X114:7
DO X114:8
Single output X114:8
DO X114:9
Single output X114:9
SSMx.21 SSM2 input
Sets the digital input connected to the SSM2
function.
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...