68 Safety functions
STO function
The operation of the STO function when the SBC is not used is described in the time
diagrams and tables below. For configuration, see section
page
Without an encoder
A
): Time from the STO activation to the moment
when the safety function is completed and the STO completed indication (parameter
) goes on. You must set this to the estimated time in which the motor coasts to a
stop from the maximum speed.
B
Restart delay after STO (parameter
): Time from the STO activation to the
moment when the acknowledgment becomes allowed. With this parameter, you can
allow a restart of the drive before the motor has stopped (fly-start). You can use this
feature only in certain applications. This parameter is relevant only when an external
request activates the STO function.
Step
Description
1
The STO request is received (for example, from the I/O). The FSO activates the drive
STO function and starts counters for times A and B. STO active indication parameter
STO output (
) goes on.
2
After time B has elapsed, the acknowledgement becomes allowed as soon as the
STO request has been removed (step 4).
Note
: If an SSE or SS1 request is received while the STO function is active, the STO
function must be completed before the acknowledgement is allowed.
3
After time A has elapsed, the FSO module defines the motor as stopped and the STO
completed indication goes on.
4
The STO request is removed.
Drive STO state
& indication
4
STO request
Motor speed
Time
A
5
3
STO completed
indication
1
B
2
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...