5. Activate the SSE function. For example, press the emergency stop button, which
is wired to the FSO input for the SSE function.
6. Make sure that the drive STO is activated immediately after the SSE request.
7. Remove the SSE function user request.
8. a) If manual acknowledgement (or safebus acknowledgement) is in use: Verify by
trying to acknowledge the function, that it is not possible before the motor is in
safe state.
b) If automatic acknowledgement is in use: Make sure that the function is not
acknowledged and that the delays are correctly configured by verifying that the
drive cannot be restarted before the motor is in safe state.
Validation of the SSE with emergency ramp function
1. Make sure that the input for the SSE function is configured according to the wiring
diagram.
2. Make sure that the SSE function and SAR0 setting or time monitoring limit is
configured correctly according to your design. For a configuration example see
section
How to configure SSE with time monitoring
on page
or
configure SSE with ramp monitoring
. Check these settings:
Activation:
•
•
.
•
Note:
activation can also come from the PROFIsafe
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality:
•
= Emergency ramp
•
•
200.201 SAR0 ramp time to zero
•
SSE.16 SSE ramp zero speed delay for STO
, if used
•
•
•
a) With ramp monitoring:
-
= Ramp
SARx.02 SAR initial allowed range
SARx.11 SAR0 max ramp time to zero
SARx.12 SAR0 max ramp time to zero
.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...