How to configure safety relays
If you want to control a safety relay or contactor with the FSO module, define the use
of the related I/O with these parameters. See also section
on page
Do not configure a safety function activation to a safety relay feedback. In addition,
you have to connect the safety relay to the desired safety function. Set the same
digital output as you set for the safety relay as the output of the desired safety
function. In this example, safety relay 1 is connected to the SBC function.
Index
Name/Value
Description
Sets the digital output connected to the safety relay 1.
DO X113:8 &
X114:8
Redundant output X113:8 & X114:8
Sets the digital feedback input of safety relay 1.
DI X113:4
Single input X113:4
Sets the type of the feedback signal for safety relay 1.
Mechanically
linked NC
contacts
Feedback of the safety relay is NC (inverted state compared
with the relay).
Sets the digital output for safety relay 2.
None
No output connected
Sets the digital feedback input of safety relay 2.
None
No input connected
Sets the type of the feedback signal for safety relay 2.
Mechanically
linked NC
contacts
Feedback of the safety relay is NC (inverted state compared
with the relay).
Index
Name/Value
Description
Sets the digital output that is connected to the SBC output
(brake relays).
DO X113:8 &
X114:8
Redundant output X113:8 & X114:8
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...