470 Verification and validation
Validation of the SSE function
Always configure and validate the SSE function. Test the SSE function always with a
separate function request, for example by activating it via a suitable input configured
for the SSE.
Internal diagnostics of the FSO module, trip limit hit cases and PROFIsafe
passivation will trigger the SSE function even if you have not defined an external
request signal for the SSE. For example, the FSO module activates the SSE function
if an SLS trip limit hit occurs. The SSE function must be configured as SSE with STO,
SSE with ramp stop, or SSE with time monitoring, based on the risk assessment of
the application. The configuration must also cover the worst-case situation in case
any of the issues above triggers the SSE function, or in case any stopping function
with the SSE triggers the SSE.
Validation of the SSE with immediate STO function with safe speed estimation
1. Make sure that the input for the SSE function is configured according to the wiring
diagram.
2. Make sure that the SSE function is configured correctly according to your design.
For a configuration example, see chapter
How to configure SSE with immediate
on page
). Check these settings:
Activation:
•
•
.
•
Note:
Activation can also come from the PROFIsafe.
Acknowledgement:
•
•
if manual acknowledgement is
used.
Functionality:
•
Immediate STO
•
Time to zero speed with STO and modoff
. (
is the time in
which the motor coasts to a stop from the maximum speed.)
Indication:
•
•
•
3. If you made any changes, download and validate the configuration with the Drive
composer pro PC tool.
4. Make sure that you can run and stop the motor freely. Start the drive.
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...