Parameters 445
50…59,000 ms
Time
SAFEIO.33 DI X113:1 diag pulse
on/off
Sets the diagnostic pulse of digital input
X113:1 on or off.
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.34 DI X113:2 diag pulse
on/off
Sets the diagnostic pulse of digital input
X113:2 on or off.
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.35 DI X113:3 diag pulse
on/off
Sets the diagnostic pulse of digital input
X113:3 on or off.
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.36 DI X113:4 diag pulse
on/off
Sets the diagnostic pulse of digital input
X113:4 on or off
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.37 DI X114:1 diag pulse
on/off
Sets the diagnostic pulse of digital input
X114:1 on or off.
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.38 DI X114:2 diag pulse
on/off
Sets the diagnostic pulse of digital input
X114:2 on or off.
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.39 DI X114:3 diag pulse
on/off
Sets the diagnostic pulse of digital input
X114:3 on or off
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.40 DI X114:4 diag pulse
on/off
Sets the diagnostic pulse of digital input
X114:4 on or off
Off
Diagnostic pulse off
On
Diagnostic pulse on
SAFEIO.51 DO diagnostic pulse
length
Sets the length of the diagnostic pulse for
digital outputs.
0.5 ms
Length of the diagnostic pulse is 0.5 ms.
1 ms
Length of the diagnostic pulse is 1 ms.
2 ms
Length of the diagnostic pulse is 2 ms.
SAFEIO.52 DO diagnostic pulse
period
Sets the time during which the FSO module
must receive at least one whole diagnostic
pulse.
10,000 ms
50…59,000 ms
Time
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...