Safety functions 141
user can also set the reaction type and the delay for activating the STO indication
after the modulation loss.
For this procedure to work, at least the auxiliary power (24 V DC) to the control unit
and the FSO module must be on. For more information, see section
when modulation is lost during deceleration ramp, with ramp monitoring
on page
SLS with speed below monitored speed
This applies to both time and ramp monitoring.
A
SLS trip limit positive (parameter
B
,
- - -
SSE coast stop due to SLS trip limit hit
Motor speed
Time
1
3
2
4
A
B
SLS request
SLS monitoring
SLS indication
Manual
acknowledgment