472 Verification and validation
OR
b) With time monitoring:
-
= Time
-
Indication:
•
•
•
3. If you made any changes, download and validate the configuration with the Drive
composer pro PC tool.
4. Make sure that you can run and stop the motor freely. Start the drive and
accelerate the motor to the maximum speed of the application.
5. Activate the SSE function. For example, press the emergency stop button which
is wired to FSO module input for the SSE function.
6. Remove the SSE function user request.
7. a) If manual acknowledgement (or safebus acknowledgement) is in use: Verify by
trying to acknowledge the function, that it is not possible before the motor speed
is low enough:
•
.
•
With safety encoder:
b) If automatic acknowledgement is in use: Verify that the function is not
acknowledged before the motor is in safe state, see the conditions above.
8. Make sure that the motor speed decelerates as expected and the FSO does not
trip to the monitoring limit (ramp or time).
9. Start the drive and accelerate the motor to the maximum speed of the application.
10. Activate the SSE function. For example, press the emergency stop button which
is wired to the FSO module input for the SSE function.
11. Remove the SSE function user request.
12. Activate the coast stop of the drive.
You can, for example, cause an external fault trip in the drive. For more
information, see the drive firmware manual (Group
31 Fault functions
).
13. Make sure that the FSO trips the drive, and activates the STO function according
to the application requirements.
14. Make sure that the acknowledgement of the STO function is not possible before
the motor is in safe state
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...