414 Parameters
SBC.13 SBC time to zero
speed
Sets the estimated time from the SBC
activation to the moment when the safety
function is completed and the STO
completed indication (parameter
)
goes on (ie, motor has stopped and the
system can be set to a safe state).
Must be configured to the estimated time in
which the external brake decelerates the
motor to a stop from the maximum speed.
The total delay from the moment the FSO
module has activated the drive STO function
until the system is in safe state becomes:
(
Note
: If the value of
(
) is less than 800 ms (the feedback
delay), the total delay becomes:
(
) + 800 ms.
When an encoder is used: This parameter is
relevant only if there is an encoder failure
and the FSO module activates the STO and
SBC functions.
3,600,000
ms
0…3,600,000 ms
Time
SBC.14 STO SBC speed
Sets the speed limit below which the FSO
module activates the brake (SBC) in the
STO function.
Requires that an encoder is
is set to value
Speed limit
. If the value
is
0.0 rpm
, this feature is not in use.
Note
: This is the absolute value. The same
value is used in both positive and negative
directions.
0.0 rpm
0.0…1000.0 rpm
Speed
SBC.15 SSE/SS1 SBC
speed
Sets the speed below which the FSO
module activates the brake (SBC) while
ramping in the SSE and SS1 functions. If the
value is
0.0 rpm
, this feature is not in use.
Note
: This is the absolute value. The same
value is used in both positive and negative
directions.
0.0 rpm
0.0…1000.0 rpm
Speed
SBC.21 SBC output
Sets the digital output that is connected to
the SBC output (brake relays).
None
No output connected
DO X113:7 & X114:7 Redundant output X113:7 & X114:7
Index
Name/Value
Description
Factory
default
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...