Safety functions 59
Status bit indication
PROFIsafe status bit indication of the safety function is relevant when the FSO
module is part of a PROFIsafe control system. These are safety-related indications.
Note:
Status and control words (see
on page
) are not
safety-related indications, and they can be used for monitoring purposes only. They
are not allowed to be used as safe status and control indications in PROFIsafe/safety
systems.
STO, SS1, SSE, POUS functions
States of the configured and connected functions are indicated with FSO digital
outputs and fieldbus status signals when the function is started:
• Stopping functions (SSE and SS1) are always started and their active state
indicated immediately (the monitoring method depends on the configuration)
(parameters
• The drive STO state is indicated when the drive STO circuit is open (parameter
and octet 0 bit 7 STO_active).
Note:
When the SBC is activated before the drive STO, the drive STO active state
is indicated after a delay (parameter
Note:
SBC active state is indicated only with status bit (octet 0 bit 6 SBC_active).
• POUS active state is indicated immediately when requested from an input
).
• Ramp monitoring (SAR0 and SAR1, see section
) is
not indicated.
The FSO module switches off the digital output indications (SSE, SS1 and POUS
functions) when the function is acknowledged.
Stop completed indications are activated when the stopping function has completed,
but is not yet acknowledged. There are separate indications for each stopping
function STO, SSE and SS1 (parameters
) and one common for all of
). The FSO module switches off
the indications when the function is acknowledged.
The completed indication of the POUS function (parameter
) is activated after the time defined by parameter
has passed. The FSO module switches off the completed
indication when the POUS request is removed.
SLS, Variable SLS
• SLS active state is indicated when the motor speed is in the user-defined range.
The FSO module switches off the indication when the function is acknowledged or
the monitored speed exceeds the user-defined limit (this also causes the SLS to
trip, that is, the FSO module activates the SSE function).
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...