Fault tracing 491
Faults, warnings and events
Code
(hex)
Name
Cause
What to do
Faults
7A81
TUCSO fault
FSO subsystem fault
Contact your local ABB
representative.
7A8B
FSO general fault
FSO module is in the
Configuration mode.
FSO module also
generates this fault after
certain malfunctions
which the FSO module
indicates by warnings.
First the FSO module
generates a warning
indication which allows
the drive to control the
system to a safe state.
After this the drive trips.
See the warning log for more
information on the actual cause.
3)
7A90
FSO stop
completed
FSO module has
completed the STO, SS1
or SSE function.
-
1)
7A91
FSO safe speed
limit
FSO module detected an
SLS or SMS speed trip
limit violation.
Check the separate code related to
SLS and SMS functions.
See section
for limit hits and special events
on
page
2) 3)
7A92
FSO out of eme
ramp
Motor speed was not
inside the ramp window
during the SSE function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
7A93
FSO ramp
coasted
Drive coasted the motor
to stop instead of using
the ramp.
Check that the FSO module speed
limit for stopping the ramp
deceleration is not excessive
(
).
2)
7A94
FSO out of safe
ramp
Motor speed was not
inside the ramp window
during the SS1 function.
Make sure that the drive can
decelerate the load using the ramp
time (
).
2)
7A96
FSO out of SDI
SDI positive or SDI
negative exceeded the
tolerance limit to the
forbidden direction.
Make sure that SDI tolerance values
are defined properly.
Check limits of the drive.For example,
see the usage of DC hold from the
drive firmware manual.
2)
Summary of Contents for FSO-21
Page 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Page 4: ......
Page 16: ...16 Safety instructions ...
Page 34: ...34 Safety information and considerations ...
Page 52: ...52 Overview ...
Page 236: ...236 PROFIsafe ...
Page 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Page 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Page 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Page 286: ...286 PROFIsafe ...
Page 304: ...304 Installation ...
Page 400: ...400 Configuration ...
Page 488: ...488 Verification and validation ...
Page 506: ...506 Fault tracing ...
Page 514: ...514 Maintenance ...
Page 536: ...536 Technical data ...